6K/10K Rack/Tower Online UPS Uninterruptible Power Supply System Version: 1.2User Manual
2-3-2 Rack Installation Please follow below steps to mount UPS into 19” rack or rack enclosure. Step 1: Attach mounting ears to the side mounting h
regulations. Warning: ● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for other external ba
3. Operations 3-1. Operating Mode/Status Description Mode/Status Description UPS Power On When UPS is powered on, it will enter into this mode for a f
There are 4 buttons on front panel. 3-3. LED Indicators There are 4 LEDs on front panel to show the UPS working status: Mode
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be starting up with beeping once. You could also enter the “control
prolong the backup time. If there is no more load to be taken off at that time, you have to shut down all loads as soon as possible to protect the dev
3-5-9. Changing battery quantity (number) The default battery (12V) quantity of this UPS system is 20 (for one series), but 18, 19 could also be appli
3-7. LCD Operation The entire LCD structure is demonstrated as diagram below: Main Interface Control Measurement Information Setting AlarmPage 1: Inpu
3) When the front panel is not operated for 10 minutes, the display page will return back to home page; 4) Press the “UP” or “DOWN” button to enter
→ → NOTE: You may simply turn on UPS by pressing “ON/ENTER” button in home page. It’s not necessary to enter control menu to turn on the UPS.
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully th
→ → 4) Para Unlock It’s to allow UPS startup with parallel function. It only appears when the LCD shows the warning of “3F: Para Protect”. It m
3-7-2-4. Information Information displays all parameter setting value and status. Press “UP” or “DOWN” to explore the pages. 3-7-2-5. Setting This m
1) Bypass setting Interface Description 1. Status (only available in bypass / AC mode) 1.1 Open/Forbid: Open: Bypass allowed. When selected, UPS wil
3) Output setting (only available or effective on bypass mode) Interface Description 1. Volt: 208: Presenting the rated output voltage with 208Vac 2
5) Calibration Interface Description 1. Batt: Calibrate the battery voltage measurement. Calibration range is from 0V to 5.7V. The default value is
Backup Time Parameters Setting: Batt Groups: Set the number of battery group ranging from 1 to 6. The default value is 1 group;
3-7-2-6. Alarm page This page records and displays the faults or warning events happened in history.
4. Trouble Shooting 4-1. Warning status When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems with UP
Warning 0D: Over Temp The internal temperature is too high and reach the warning level: 1) Maybe the environment is hot; 2) Maybe the fan is
Fault 04: Bus Unbalance 1) The load is special or abnormal, so the internal positive and negative DC bus voltages are unbalanced. 2) The in
Table of Contents 1. Safety and EMC instructions ... 4 1-1. Transportation and Storag
5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location.
6. Specifications MODEL 6KRT(L) 10KRT(L) CAPACITY* 6000 VA / 5400 W 10000 VA / 9000 W INPUT Voltage Range Low Line Loss 110 VAC ± 3 % at 50% Load;
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the uni
1-4. Connection Warnings • There is no standard backfeed protection inside, please isolate the UPS before working according to this circuit. The iso
time since this would cancel the protective earth of the UPS system and of all connected loads. If the external battery cabinet is connected, the
2. Installation There are two types: standard and long-run models. Please refer to the following model table. Model Type Model Type 6KRT Standard mode
Diagram 3: Battery Pack Rear Panel 1. RS-232 communication port 2. USB communication port 3. EPO (Emergency Power Off) connector 4. Shar
2-3. Rack/Tower Installation 2-3-1 Tower Installation The UPS system is shipped with two sets of feet and 6 extensions (2 short extensions plus 4 long